Vaillant F.22 fault codewhat it means and how to fix it

Get it checkedHeat pumpAll three generations. On the aroTHERM plus and aroTHERM split indoor units the M32 and F.22 thresholds and the "inform your competent person" instruction are published; on the earlier aroTHERM monobloc the appendix lists F.022 "Water pressure too low" and the operating instructions say the product switches off below 0.5 bar and to top up with water. Printed as F.22 on the display, F.022 in the appendix table and F.723 in the operating instructions’ troubleshooting section.Last updated

Water pressure too low. Vaillant publish exact thresholds and two instructions: the indoor unit manual says inform your competent person; Vaillant UK’s fault page lets a competent owner top up to 1 to 1.5 bar.

Take care

Some of this is safe to check yourself, but the repair itself is not. If the fault comes back after one reset, stop resetting it and get an F-Gas certified heat pump engineer to look at the Vaillant properly.

What F.22 means

F.22 is the heat pump switching itself off because the heating water pressure has fallen too far, and the thresholds are published precisely. Below 0.7 bar you get a maintenance message, M32, which goes out on its own once pressure rises above 0.7 bar again. Below 0.5 bar for longer than one minute, the fault message F.22 and the current filling pressure appear alternately on the display, and that goes out when pressure rises back above 0.5 bar. Vaillant give 1 to 1.5 bar as the correct cold filling pressure, higher on a house of several storeys, and 0.7 bar as the minimum operating pressure.

What to do about it is where Vaillant’s own documents part company, and you should know all three. The operating instructions for the uniTOWER plus and the hydraulic station — the indoor units on aroTHERM plus and aroTHERM split systems — say that if the filling pressure falls below the minimum the heat pump is switched off automatically, and then: inform your competent person so that he can top up the heating water. The operating instructions for the earlier aroTHERM monobloc say the opposite in three words, "Top up with water", under checks carried out by the operator. And Vaillant UK’s owner-facing fault code page splits it by pressure: if the gauge shows less than 1 bar, this can be solved without an engineer if you are competent to do so, by locating the filling loop and slowly raising the pressure to between 1 and 1.5 bar, at your own risk; if it shows more than 1 bar and the fault is still there, it is a case for a Vaillant engineer, because the causes then are a faulty pressure sensor or its wiring, or the expansion vessel.

Two things are worth adding that Vaillant do not spell out on that page. Their own manuals strongly recommend antifreeze in parts of the installation at risk of frost, and some aroTHERM plus systems have a primary circuit filled with a propylene glycol mixture — topping those up with plain water dilutes the protection, which is a good reason to know what your system holds before you open a filling loop. And a heat pump circuit has a great deal more pipework than a boiler’s, so pressure that keeps needing attention means a leak to find rather than a level to correct. One last trap: the troubleshooting section of the same indoor unit manuals heads this fault F.723, "Building circuit: Pressure too low", while the display and the appendix call it F.22 and F.022. They are the same fault.

What causes it

Causes of the Vaillant F.22 fault code, most common first
CauseWhat is actually happeningHow likely
A leak somewhere in the heating circuitVaillant’s appendix gives pressure loss in the building circuit due to leakages or air pockets as the first cause. A heat pump circuit has far more pipework than a boiler system, so there is more to leak from.Common
Air vented out after recent workThe other half of Vaillant’s first cause. Any work on radiators or valves releases air that was taking up volume, and pressure drops as it goes.Common
Pressure sensor or its wiringNamed in both the appendix and on Vaillant UK’s page: a defective building circuit pressure sensor, or loose, disconnected or faulty wiring to it. This is the version where the gauge reads fine and the fault is still on the screen.Occasional
Expansion vessel losing its chargeOn Vaillant UK’s cause list. Shows as pressure that swings widely between cold and hot rather than simply falling. An installer job.Occasional
Pressure relief valve passingUsually gives itself away as an occasional trickle from an outside discharge pipe.Occasional

What to try yourself

  1. Read the pressure. On the indoor unit it is under Menu, Live Monitor, Water pressure; some systems also have a gauge. Below 0.5 bar is what produces this fault; below 0.7 bar produces the M32 maintenance message instead; 1 to 1.5 bar cold is where Vaillant want it.

  2. Look for the leak. Check around radiator valves, under the indoor unit, and at any visible pipework — a small weep that dries between visits leaves a stain or a bloom of limescale.

  3. Check whether an outside discharge pipe has been dripping. That points at the pressure relief valve rather than a leak in the house.

  4. Decide whether to top up yourself. Vaillant UK’s page says you may, if you are competent, by locating the filling loop and slowly raising the pressure to between 1 and 1.5 bar. The indoor unit manual says to inform your competent person instead. If you know where the filling loop is, know the system is plain water, and this is the first time, the top-up is the same job as on a boiler. If any of those is not true, ring your installer.

    Vaillant recommend antifreeze in parts of a system at risk of frost, and some aroTHERM plus installations have a glycol-filled primary circuit. Adding plain water to those dilutes the protection. If you do not know what your system was filled with, that is the reason to make the call rather than open the valve.
  5. If the pressure is above 1 bar and F.22 is still showing, do not keep adding water. Vaillant UK make that a Vaillant engineer case — the pressure sensor, its wiring or the expansion vessel — and topping up further only overpressurises a system that is not actually low.

  6. Tell whoever attends how often it has happened. Pressure that needs topping up more than about once a year means a leak to find rather than a level to correct, and Vaillant’s own instruction is to identify and eliminate the reason for the loss.

Get an F-Gas certified heat pump engineer to look at your Vaillant F.22

We do not pass enquiries to a repair firm, so there is no form here. When you book an F-Gas certified heat pump engineer, tell them the make, the model and the exact code or message on the display, and ask whether they carry parts for this make — that is what turns one visit into a repair rather than a quote.

What it costs to fix

Typical repair cost

£0–£450

Time on site

15 minutes

Nothing if you top it up yourself. An installer visit to repressurise and check is typically £90 to £150. Finding and fixing a leak, or replacing an expansion vessel or pressure sensor, runs from £150 to £450 depending on where it is.

Typical UK prices including parts and labour, updated September 2026. Your quote may differ.

Parts you may need

We may earn a commission if you buy a part through one of these links. It does not change what you pay, and it does not affect which parts we list.

Expansion vessel (8 litre, sealed system)

EV-8L£35–£85Plumbing merchant

Price checked 28 September 2026

Own this appliance and had this code? . Nothing is published until a person has read it.

Common questions about Vaillant F.22

Can I top it up myself or not?

Vaillant say both, in different documents. The uniTOWER plus and hydraulic station operating instructions tell you to inform your competent person so that he can top up the heating water; the earlier aroTHERM monobloc’s operating instructions say "top up with water"; and Vaillant UK’s fault code page says an owner who is competent may use the filling loop to bring it to 1 to 1.5 bar, at their own risk, with a homeowner technical support line if you need help. The sensible reading is that a one-off top-up on a plain-water system is yours if you want it, and anything involving glycol, repeat losses or a pressure that is already above 1 bar is the installer’s.

What is the difference between M32 and F.22?

They are two thresholds on the same measurement. M32 is a maintenance message below 0.7 bar and the unit keeps running. F.22 is a fault below 0.5 bar held for more than a minute, and the heat pump switches off. Both go out on their own if pressure comes back up above their threshold — or, for F.22, once the blocking time has elapsed.

My manual says F.723. Is that the same thing?

Yes. The troubleshooting section of the uniTOWER plus and hydraulic station operating instructions heads the low pressure fault F.723, "Building circuit: Pressure too low", while the display shows F.22 and the appendix table lists it as F.022. The wording under all three is the same fault and the same thresholds.

Written by

Andrew Pickett

Researcher and writer

Last updated

Technical review

Not reviewed by an engineer

No engineer has read this page. Severity follows what the manufacturer publishes, and we would rather tell you that than let a byline imply a sign-off.

What we check instead

Sources and how we verified this

We establish the facts from the sources below and then write the explanation ourselves. We do not copy manufacturer wording and we do not host their manuals.

  • Manufacturer technical and service documentation
  • Manufacturer support portal

This page has not been reviewed by an engineer, and we would rather tell you that than imply otherwise. The severity rating follows what the manufacturer publishes: where they say isolate the appliance and call someone, so do we.

Read our full verification process

Was this page helpful?