Glow-worm F.00 fault codewhat it means and how to fix it

Get it checkedBoilerF.00 on Energy, Ultimate, Easicom, Betacom3/4 and Compact · F00 on Ultracom2, Betacom 24a/28a and Betacom2 · shown as F6 (06 on a CI display) on Ultracom, Flexicom, Ultrapower and the CI rangeLast updated

The flow temperature sensor circuit is open — plug off, wire broken or thermistor failed — so the boiler has no flow temperature and will not run. Engineer's code on every range.

Take care

Some of this is safe to check yourself, but the repair itself is not. If the fault comes back after one reset, stop resetting it and get a Gas Safe registered engineer to look at the Glow-worm properly.

Get a Gas Safe registered engineer to look at your Glow-worm F.00

We do not pass enquiries to a repair firm, so there is no form here. Find a Gas Safe registered engineer through the Gas Safe Register, and ask to see their registration card when they arrive — it is the register, not the van, that tells you they are qualified.

What F.00 means

The flow sensor is the thermistor clipped to the pipe leaving the heat exchanger, and the board reads it constantly while the burner is alight. F.00 is what an Energy, Ultimate, Easicom or Compact shows when that reading disappears. Glow-worm's Energy7 and Ultimate3 manuals give four causes in one breath: "NTC plug not plugged in or has come loose, multiple plug on the PCB not plugged in correctly, interruption in cable harness, NTC sensor defective".

The Compact manual calls it "flow temperature sensor interruption" and pairs each cause with a check — the plug, the multiple plug, the harness, and finally the sensor. Glow-worm's homeowner page keeps it to one line, "the flow temperature sensor has been interrupted", and sends the reader to an engineer, because nothing on the list can be reached with the case on.

On the two-digit Ultracom2, Betacom 24a/28a and Betacom2 the same fault is F00, "flow heating temperature sensor fault — sensor open circuit". The Ultracom, Flexicom, Ultrapower and CI generations number the flow thermistor differently: F6 on the trade tables, shown as 06 on a CI-range display, so an owner of one of those boilers should read this page with that in mind. Whatever the number, the fix is the same small part or a reseated plug.

What causes it

Causes of the Glow-worm F.00 fault code, most common first
CauseWhat is actually happeningHow likely
Sensor plug loose or offGlow-worm's first cause on every current manual. The NTC plug is small and sits where a service engineer's hand passes; one knocked loose reads as an open circuit the moment the board next looks for it.Common
Thermistor failed openThe sensor is a sealed bead that ages with heat. An open-circuit reading against the resistance table in the installation manual confirms it, and it is replaced rather than repaired.Common
Break in the harness or the multiple plug on the boardThe two remaining causes in Glow-worm's list. A harness chafed on the casing, or the multi-way plug at the PCB not fully home, gives the same symptom as a dead sensor and is checked first because it costs nothing.Occasional

Can you fix it yourself?

What it costs to fix

Typical repair cost

£80–£160

Time on site

45 minutes

A flow thermistor fitted £80–£160 including the call-out. A harness repair sits inside the same range; a board is a different job and a different figure.

Typical UK prices including parts and labour, updated September 2026. Your quote may differ.

Parts you may need

We may earn a commission if you buy a part through one of these links. It does not change what you pay, and it does not affect which parts we list.

Glow-worm flow or return temperature sensor (clip-on NTC)

£12–£35Authorised Glow-worm parts distributor

Price checked 28 September 2026

Own this appliance and had this code? . Nothing is published until a person has read it.

Own a Glow-worm boiler? Save it and its codes come first next time.

Common questions about Glow-worm F.00

Will the boiler run at all with F.00?

No. Without a flow temperature the board has no way to stop the heat exchanger overheating, so it locks out until the sensor is seen again.

My Ultracom shows F6, not F.00. Is that the same thing?

Yes. On the Ultracom, Flexicom, Ultrapower and CI ranges the flow thermistor fault is numbered F6 — 06 on a CI display — and F00 does not appear in those tables. The part and the fix are the same.

Is F.00 the same as F.01?

F.01 is the return sensor, F.00 the flow. Same failure, different pipe. Glow-worm list identical causes for both.

Written by

Andrew Pickett

Researcher and writer

Last updated

Technical review

Not reviewed by an engineer

No engineer has read this page. Severity follows what the manufacturer publishes, and we would rather tell you that than let a byline imply a sign-off.

What we check instead

Sources and how we verified this