Vaillant S.41 status codewhat it means
A status, not a lockout: the heating water pressure is too high, above about 2.8 bar. Usually an over-filled system or a tired expansion vessel, and the safety valve will discharge above 3 bar.
Take care
What S.41 means
S.41 is the status "Water pressure too high — the system pressure is too high", and the ecoTEC exclusive manual gives the figure: "water pressure > 2.8 bar". The boiler is not locked out. It is telling you that the sealed heating system is carrying more pressure than it should, and that the next stop is the pressure relief valve, which opens at 3 bar and dumps water through the copper pipe that ends outside.
Vaillant's operating instructions for the ecoTEC sustain put the householder response in one line: "the system pressure is too high: > 0.3 MPa (> 3 bar) — wait until the excess heating water has flowed out through the expansion relief valve", which is honest about what will happen but not something to rely on twice, because a relief valve that has lifted often fails to reseal and then weeps for good. The two common causes are simple. The system was filled too far, to 2 bar or more when cold, so that ordinary expansion as it heats pushes it towards 3 bar; or the expansion vessel has lost the air charge that lets it absorb that expansion, so the pressure swings between low when cold and very high when hot.
A combi has a third route: a pinhole in the plate heat exchanger or a passing filling loop lets mains water at 3 or 4 bar creep into the heating side, and the pressure climbs over days with nothing switched on. F.74 is the fault version, raised when the pressure sensor's signal is too strong, and its remedy in the installer table is "drain water, check the water pressure sensor". The 2022 ecoTEC plus shows S.041.
What causes it
| Cause | What is actually happening | How likely |
|---|---|---|
| Over-filled when topping up | Filled to 2 bar or above with the system cold. Heating it adds the best part of a bar, and 2.8 arrives before the radiators are hot. | Common |
| Expansion vessel lost its charge | Without air behind the diaphragm the vessel cannot absorb expansion. Pressure climbs steeply as the boiler heats and falls back when it cools, and the relief valve discharges each cycle. | Common |
| Filling loop left open or passing | A loop with both valves not fully closed, or a worn valve, feeds mains pressure into the heating. Pressure rises with the boiler off and keeps rising. | Occasional |
| Plate heat exchanger leaking mains into the heating | A combi-only cause. A pinhole between the two sides lets cold mains through at mains pressure. Pressure creeps up over days, and hot water may run tepid at the same time. | Rare |
What to try yourself
Check both valves on the filling loop are fully closed, and if your loop is the flexible detachable kind, that it is disconnected. Then read the pressure with the boiler cold. Vaillant's range is 1.0 to 2.0 bar cold; the top of the bar graph on the display marks 2.0.
If it is above 2.0 bar cold and you filled it recently, let a little water out at a radiator bleed valve into a cloth or cup until the display reads about 1.2 to 1.5 bar. Do it slowly and stop early; it is easier to add than to remove.
Do not open the boiler's pressure relief valve to lower the pressure. It rarely reseals properly once lifted by hand and will drip outside for good.Watch the pressure over the next few heating cycles. If it climbs above 2.5 bar every time the boiler is hot and falls back when cold, the expansion vessel needs recharging or replacing. If it climbs with the boiler off and the loop closed, water is getting in from the mains, and both are engineer's work.
Get a Gas Safe registered engineer to look at your Vaillant S.41
We do not pass enquiries to a repair firm, so there is no form here. Find a Gas Safe registered engineer through the Gas Safe Register, and ask to see their registration card when they arrive — it is the register, not the van, that tells you they are qualified.
What it costs to fix
Typical repair cost
£80–£450
Time on site
20 minutes
Letting a little water out costs nothing. Recharging the expansion vessel is £80 to £120; replacing it £180 to £300; a plate heat exchanger on a combi £250 to £450 fitted.
Typical UK prices including parts and labour, updated September 2026. Your quote may differ.
Parts you may need
We may earn a commission if you buy a part through one of these links. It does not change what you pay, and it does not affect which parts we list.
Expansion vessel (8 litre, sealed system)
EV-8L£35–£85Plumbing merchant
Price checked 28 September 2026
Pressure relief valve, 3 bar
PRV-3B£18–£42Plumbing merchant
Price checked 28 September 2026
Vaillant ecoTEC water pressure sensor
0020059717£26–£54Authorised Vaillant parts distributor
Price checked 28 September 2026
Own this appliance and had this code? . Nothing is published until a person has read it.
Related Vaillant fault codes
- F.22Get it checkedThe boiler has shut down because there is not enough water in the system. Pressure has dropped below roughly 0.5 bar and it will not fire until you top it up.Related: water pressure
- F.75Get it checkedThe boiler cannot detect a rise in pressure when the pump starts, so it has locked out. Usually a failed pressure sensor or a pump that is not moving water.Related: water pressure
- S.53Get it checkedNot a fault. Your boiler is in a deliberate waiting period because the gap between flow and return temperatures is too wide, which points at poor circulation.Related: water pressure
- F.73Get it checkedThe pressure sensor signal is out of range at the low end. Usually the sensor or its wiring, rather than the pressure itself.Related: water pressure
- F.74Get it checkedThe water pressure sensor is sending a signal that is too high to be genuine. This is a wiring or sensor fault, not high system pressure.Related: water pressure
- S.76Get it checkedA service message, not a lockout: the heating water pressure has dropped and Vaillant want it topped up. The boiler is still running, but below 0.5 bar it will stop with F.22.Related: water pressure
Own a Vaillant boiler? Save it and its codes come first next time.
Related guides
Common questions about Vaillant S.41
Will the boiler stop?
Not at S.41; it is a status and the boiler carries on. Above 3 bar the safety valve opens and lets water out until the pressure falls. If the pressure sensor reads very high the boiler raises F.74 and does stop. Either way the cause wants fixing before the valve is asked to do that again.
It was fine for years. Why now?
Expansion vessels lose their air charge slowly through the diaphragm; most need re-pressurising after five to ten years. The first sign is a pressure that swings much more than it used to between cold and hot, and a puddle under the discharge pipe outside.
Can I keep letting water out?
As a one-off after over-filling, yes. As a routine, no: if you are bleeding water out every week, something is adding it, or the vessel is not absorbing expansion, and each cycle wears the safety valve and brings fresh, oxygenated water into the system.
Technical review
Not reviewed by an engineer
No engineer has read this page. Severity follows what the manufacturer publishes, and we would rather tell you that than let a byline imply a sign-off.
Sources and how we verified this
We establish the facts from the sources below and then write the explanation ourselves. We do not copy manufacturer wording and we do not host their manuals.
- Manufacturer technical and service documentation
This page has not been reviewed by an engineer, and we would rather tell you that than imply otherwise. The severity rating follows what the manufacturer publishes: where they say isolate the appliance and call someone, so do we.