Mitsubishi Electric L3 fault codewhat it means and how to fix it
Circulation water temperature overheat protection. The flow rate has probably dropped, and Mitsubishi list three things to check: a water leak, a blocked strainer and the pump.
Take care
What L3 means
L3 is the FTC protecting the system because the circulation water got too hot, and Mitsubishi’s explanation is a flow one: the flow rate may be reduced. The cylinder unit service manual gives the trigger, the flow or return water thermistor reading 85 °C or more for ten consecutive seconds. Water that is not moving fast enough through the plate heat exchanger picks up too much heat on each pass, the temperature climbs past that threshold, and the FTC stops the heat pump before the water boils or the exchanger is damaged. Their three published checks in the FTC manual are for water leakage, a strainer blockage and the water circulation pump function, and there is a fourth line in brackets that saves a lot of worry: the error code may display during filling of the primary circuit, and the remedy is to complete the filling and reset the error. That is why L3 turns up on commissioning day and after a repair that drained the system, and why an L3 the day after the installer left is usually a partly filled circuit rather than anything broken.
Mitsubishi’s UK lookup adds the other possibility, that the flow pipe thermistor is reading the wrong value, and sends the engineer to compare its reading in the service menu; the service manual’s longer list runs from insufficient system head and reduced flow, through valve and actuator faults and a stuck booster heater relay, to a detached or faulty thermistor and the board.
Several other codes point back here. L6, circulation water freeze protection, L9, low flow detected by the flow sensor, and P6, anti-freeze protection of the plate heat exchanger, all carry the instruction "See Action for L3", because the same reduced flow produces overheating in one direction and freezing in the other depending on what the heat pump was doing. What reduces flow in a house is mostly ordinary: too many radiator valves shut, an underfloor manifold with every loop closed, a zone valve that has stuck, air in the pump, or a strainer that has collected the debris of an old system. The strainer and the pump are installer work on a pressurised sealed circuit; the valves and the pressure gauge are yours.
What causes it
| Cause | What is actually happening | How likely |
|---|---|---|
| Too little of the system open to flow | Thermostatic valves all closed on a mild day, an underfloor manifold shut down, or a zone valve stuck. The commonest way to reduce flow without anything failing. | Common |
| Strainer blocked | Mitsubishi’s second check. The filter on the return collects magnetite and debris, and an older heating system retrofitted to a heat pump fills it quickly. | Common |
| Primary circuit not fully filled or losing water | Mitsubishi’s first check and their bracketed note. Air in the system after filling, or a leak that has let pressure fall, both reduce circulation. | Occasional |
| Circulation pump not working properly | Mitsubishi’s third check. A pump running slow, seized after a summer idle, or set to too low a speed for the system. | Occasional |
| Flow thermistor reading wrongly | The lookup’s other cause and the service manual’s ninth: the water was never that hot, but THW1 or THW2 says it was. Found by comparing the reading with a thermometer. | Occasional |
What to try yourself
Read the pressure gauge on the cylinder unit or hydrobox. If it is below the band marked or below what the installer told you, the circuit has lost water or was never fully filled, which is the case Mitsubishi single out.
Open more of the system. Turn a few radiator valves fully up, check the underfloor manifold has loops open, and make sure any zone valve you can see is not stuck shut.
Look for water where there should not be any: under the cylinder unit, at radiator valves, at the outdoor pipework. A leak is Mitsubishi’s first check.
Do not open the strainer or bleed the pump yourself. The circuit is pressurised and the water can be very hot.Reset the code once from the controller. If it returns with the pressure normal and the system open, call your installer to check the strainer and the pump.
Get an F-Gas certified heat pump engineer to look at your Mitsubishi Electric L3
We do not pass enquiries to a repair firm, so there is no form here. When you book an F-Gas certified heat pump engineer, tell them the make, the model and the exact code or message on the display, and ask whether they carry parts for this make — that is what turns one visit into a repair rather than a quote.
What it costs to fix
Typical repair cost
£0–£250
Time on site
20 minutes
Nothing if the cause was closed valves or an unfinished fill. A strainer clean and system check is typically £90 to £150. A replacement circulation pump is £200 to £250 fitted on most systems.
Typical UK prices including parts and labour, updated September 2026. Your quote may differ.
Own this appliance and had this code? . Nothing is published until a person has read it.
Related Mitsubishi Electric fault codes
- L9Get it checkedLow flow on the primary circuit. Formally an installer job, but the causes are things you can often see — a dirty filter, a closed valve, air after radiator work.Related: water flow
- U1Get it checkedHigh pressure: the outdoor unit’s 63H pressure switch has tripped, at 4.15 MPa on R410A and R32 Ecodans and 3.2 MPa on the R290 range. Mitsubishi say it is usually water flow.Related: same brand
- No code and nothing happeningGet it checkedMitsubishi resolve four in five support calls on the phone, and publish the four common issues behind them. Three take two minutes and none of them is a code.Related: same brand
- EFGet it checkedA code Mitsubishi define as "non defined": noise on the wiring between the controller, the FTC and the outdoor unit. Their published remedy is to power the Ecodan down for thirty seconds.Related: same brand
- Outdoor unit failureGet it checkedAny code starting U, F or A means the outdoor unit; Mitsubishi publish that rule themselves. It is the refrigerant side: F-Gas work on R410A and R32 Ecodans, trained-installer work on the R290 range.Related: same brand
- J1Get it checkedThe wireless receiver cannot hear the wireless room controller. Mitsubishi’s first check is the controller’s batteries, and J1 to J8 all mean the same thing.Related: same brand
Own a Mitsubishi Electric heat pump? Save it and its codes come first next time.
Related guides
Common questions about Mitsubishi Electric L3
The system was only installed or repaired yesterday. Is L3 serious?
Probably not. Mitsubishi say in the manual itself that L3 may display during filling of the primary circuit, and that the fix is to complete the filling and reset the error. Tell the installer; it is usually air still working its way out.
Is L3 the same as L9?
They are two ends of one problem. L9 is the flow sensor or switch directly detecting low flow. L3 is the consequence: water moving too slowly gets too hot. Mitsubishi send the engineer to the same three checks for both.
Can I keep using the hot water?
The heat pump stays off until the code is cleared and the cause dealt with, so do not leave it more than a day or two. Mitsubishi do not publish what else keeps running while L3 is showing; if your cylinder has an immersion heater with its own switch, that is your stopgap for hot water, at mains-electric cost.
Technical review
Not reviewed by an engineer
No engineer has read this page. Severity follows what the manufacturer publishes, and we would rather tell you that than let a byline imply a sign-off.
Sources and how we verified this
We establish the facts from the sources below and then write the explanation ourselves. We do not copy manufacturer wording and we do not host their manuals.
- Manufacturer technical and service documentation
- Manufacturer support portal
This page has not been reviewed by an engineer, and we would rather tell you that than imply otherwise. The severity rating follows what the manufacturer publishes: where they say isolate the appliance and call someone, so do we.