Mitsubishi Electric L3 fault codewhat it means and how to fix it

Get it checkedHeat pumpAll Ecodan systems with an FTC controller; the row is worded the same in the FTC4, FTC5, FTC6 and FTC7 tables, and the 85 °C trigger is from the FTC7 cylinder unit service manual. The primary-circuit filling note is Mitsubishi’s own and applies particularly to new installations and systems recently drained for repair.Last updated

Circulation water temperature overheat protection. The flow rate has probably dropped, and Mitsubishi list three things to check: a water leak, a blocked strainer and the pump.

Take care

Some of this is safe to check yourself, but the repair itself is not. If the fault comes back after one reset, stop resetting it and get an F-Gas certified heat pump engineer to look at the Mitsubishi Electric properly.

What L3 means

L3 is the FTC protecting the system because the circulation water got too hot, and Mitsubishi’s explanation is a flow one: the flow rate may be reduced. The cylinder unit service manual gives the trigger, the flow or return water thermistor reading 85 °C or more for ten consecutive seconds. Water that is not moving fast enough through the plate heat exchanger picks up too much heat on each pass, the temperature climbs past that threshold, and the FTC stops the heat pump before the water boils or the exchanger is damaged. Their three published checks in the FTC manual are for water leakage, a strainer blockage and the water circulation pump function, and there is a fourth line in brackets that saves a lot of worry: the error code may display during filling of the primary circuit, and the remedy is to complete the filling and reset the error. That is why L3 turns up on commissioning day and after a repair that drained the system, and why an L3 the day after the installer left is usually a partly filled circuit rather than anything broken.

Mitsubishi’s UK lookup adds the other possibility, that the flow pipe thermistor is reading the wrong value, and sends the engineer to compare its reading in the service menu; the service manual’s longer list runs from insufficient system head and reduced flow, through valve and actuator faults and a stuck booster heater relay, to a detached or faulty thermistor and the board.

Several other codes point back here. L6, circulation water freeze protection, L9, low flow detected by the flow sensor, and P6, anti-freeze protection of the plate heat exchanger, all carry the instruction "See Action for L3", because the same reduced flow produces overheating in one direction and freezing in the other depending on what the heat pump was doing. What reduces flow in a house is mostly ordinary: too many radiator valves shut, an underfloor manifold with every loop closed, a zone valve that has stuck, air in the pump, or a strainer that has collected the debris of an old system. The strainer and the pump are installer work on a pressurised sealed circuit; the valves and the pressure gauge are yours.

What causes it

Causes of the Mitsubishi Electric L3 fault code, most common first
CauseWhat is actually happeningHow likely
Too little of the system open to flowThermostatic valves all closed on a mild day, an underfloor manifold shut down, or a zone valve stuck. The commonest way to reduce flow without anything failing.Common
Strainer blockedMitsubishi’s second check. The filter on the return collects magnetite and debris, and an older heating system retrofitted to a heat pump fills it quickly.Common
Primary circuit not fully filled or losing waterMitsubishi’s first check and their bracketed note. Air in the system after filling, or a leak that has let pressure fall, both reduce circulation.Occasional
Circulation pump not working properlyMitsubishi’s third check. A pump running slow, seized after a summer idle, or set to too low a speed for the system.Occasional
Flow thermistor reading wronglyThe lookup’s other cause and the service manual’s ninth: the water was never that hot, but THW1 or THW2 says it was. Found by comparing the reading with a thermometer.Occasional

What to try yourself

  1. Read the pressure gauge on the cylinder unit or hydrobox. If it is below the band marked or below what the installer told you, the circuit has lost water or was never fully filled, which is the case Mitsubishi single out.

  2. Open more of the system. Turn a few radiator valves fully up, check the underfloor manifold has loops open, and make sure any zone valve you can see is not stuck shut.

  3. Look for water where there should not be any: under the cylinder unit, at radiator valves, at the outdoor pipework. A leak is Mitsubishi’s first check.

    Do not open the strainer or bleed the pump yourself. The circuit is pressurised and the water can be very hot.
  4. Reset the code once from the controller. If it returns with the pressure normal and the system open, call your installer to check the strainer and the pump.

Get an F-Gas certified heat pump engineer to look at your Mitsubishi Electric L3

We do not pass enquiries to a repair firm, so there is no form here. When you book an F-Gas certified heat pump engineer, tell them the make, the model and the exact code or message on the display, and ask whether they carry parts for this make — that is what turns one visit into a repair rather than a quote.

What it costs to fix

Typical repair cost

£0–£250

Time on site

20 minutes

Nothing if the cause was closed valves or an unfinished fill. A strainer clean and system check is typically £90 to £150. A replacement circulation pump is £200 to £250 fitted on most systems.

Typical UK prices including parts and labour, updated September 2026. Your quote may differ.

Own this appliance and had this code? . Nothing is published until a person has read it.

Common questions about Mitsubishi Electric L3

The system was only installed or repaired yesterday. Is L3 serious?

Probably not. Mitsubishi say in the manual itself that L3 may display during filling of the primary circuit, and that the fix is to complete the filling and reset the error. Tell the installer; it is usually air still working its way out.

Is L3 the same as L9?

They are two ends of one problem. L9 is the flow sensor or switch directly detecting low flow. L3 is the consequence: water moving too slowly gets too hot. Mitsubishi send the engineer to the same three checks for both.

Can I keep using the hot water?

The heat pump stays off until the code is cleared and the cause dealt with, so do not leave it more than a day or two. Mitsubishi do not publish what else keeps running while L3 is showing; if your cylinder has an immersion heater with its own switch, that is your stopgap for hot water, at mains-electric cost.

Written by

Andrew Pickett

Researcher and writer

Last updated

Technical review

Not reviewed by an engineer

No engineer has read this page. Severity follows what the manufacturer publishes, and we would rather tell you that than let a byline imply a sign-off.

What we check instead

Sources and how we verified this