Skip to content
FaultcodeCheck

Mitsubishi Electric P6 fault codewhat it means and how to fix it

Get it checkedHeat pumpAll Ecodan systems with an FTC controller; the P6 row is worded the same in the FTC4, FTC5, FTC6 and FTC7 tables. Refrigerant is R410A on PUHZ-W and PUHZ-HW outdoor units, R32 on PUZ-WM and PUZ-HWM, and R290 on the PUZ-WZ Ecodan R290 range, which is not an F-gas.Last updated

Plate heat exchanger protection, usually against freezing. Mitsubishi send the engineer to the L3 flow checks, then to the refrigerant charge, which is F-Gas work on R410A and R32 units.

Take care

Some of this is safe to check yourself, but the repair itself is not. If the fault comes back after one reset, stop resetting it and get an F-Gas certified heat pump engineer to look at the Mitsubishi Electric properly.

Get an F-Gas certified heat pump engineer to look at your Mitsubishi Electric P6

We do not pass enquiries to a repair firm, so there is no form here. When you book an F-Gas certified heat pump engineer, tell them the make, the model and the exact code or message on the display, and ask whether they carry parts for this make — that is what turns one visit into a repair rather than a quote.

What P6 means

P6 is the FTC stopping the heat pump because the plate heat exchanger, where refrigerant meets water, was about to freeze on the water side. The FTC installation manual calls it anti-freeze protection of the plate heat exchanger and gives a two-line action: see the action for L3, and check for the correct amount of refrigerant. The cylinder unit service manual explains when it fires: the error is detected when the refrigerant temperature drops rapidly during cooling or defrosting operation, judged by the refrigerant liquid thermistor or the pressure sensor. That is the picture to hold. Cold refrigerant enters the exchanger whenever the outdoor unit runs a defrost or, on units that can do it, cooling, and if the water on the other side is barely moving, the little water that is there gives up its heat and drops toward freezing. Ice inside a plate heat exchanger splits it, and a split exchanger puts water into the refrigerant circuit, which is as expensive a failure as a heat pump has.

So the FTC watches the temperature and trips first. The L3 checks, water leakage, strainer blockage and pump function, are all about restoring flow; the service manual’s own list adds low load or inlet water that is too cold, a defective outdoor fan control, a refrigerant overcharge or a clog in the circuit, the pressure sensor and a wrong capacity code, alongside leakage or shortage of refrigerant. That last one is the line that needs a qualified engineer. A circuit low on refrigerant runs its evaporating side colder than designed, and in defrost that cold side is the plate exchanger; Mitsubishi therefore tell the engineer to correct the amount, referring to the outdoor unit manual. PUHZ-W and PUHZ-HW outdoor units contain R410A and PUZ-WM and PUZ-HWM contain R32, both fluorinated gases, so checking or correcting the charge on those is F-Gas work by law; the PUZ-WZ Ecodan R290 range holds a flammable hydrocarbon that is not an F-gas and is trained-installer work instead.

One more thing the documents disagree on. The outdoor unit service manuals define P6 as "Freezing/overheating protection is working", with a heating-mode overheat branch, and Mitsubishi’s UK lookup heads its P6 row "Over heating at the heat exchanger", with lack of water flow, air, a wrong flow setting, a blockage or a pump problem as the causes. Either way the first checks are flow. Note that P6 is a P code in name only: the other P codes on the table, P1 and P2, are thermistor failures, and P6 behaves like the L family instead, which is why we cluster it with the flow and freeze protections rather than the sensors.

What causes it

Causes of the Mitsubishi Electric P6 fault code, most common first
CauseWhat is actually happeningHow likely
Reduced water flow through the plate heat exchangerThe L3 checks Mitsubishi point to: a leak that has dropped the pressure, a blocked strainer or a pump not doing its job. Slow water freezes where fast water would not.Common
System not fully filled or air-lockedAir pockets in the exchanger leave patches of water standing still against a cold plate. Common after commissioning or a drain-down.Occasional
Refrigerant charge lowMitsubishi’s second line. Too little refrigerant makes the cold side colder than designed, and the exchanger sees it during defrost.Occasional
Repeated long defrosts in severe weatherNot on Mitsubishi’s row, but the mechanism: every defrost takes heat from the water, and a marginal flow that copes in November may not in a hard January.Rare

Can you fix it yourself?

What it costs to fix

Typical repair cost

£90–£600

Time on site

20 minutes

A strainer clean and flow check is typically £90 to £150. A refrigerant check by an F-Gas certified engineer is £120 to £250, and finding and repairing a leak adds to it. A plate heat exchanger that froze and split is the top of the range and is why the protection exists.

Typical UK prices including parts and labour, updated September 2026. Your quote may differ.

Own this appliance and had this code? . Nothing is published until a person has read it.

Common questions about Mitsubishi Electric P6

Why is a freeze code appearing when the house is warm?

Because the freezing is inside the plate heat exchanger, not in your radiators. Mitsubishi’s service manual says P6 is detected when the refrigerant temperature drops rapidly during cooling or defrosting: the refrigerant side of that exchanger runs cold, and if the water side is barely moving it drops toward zero even though the rest of the system is at sixty degrees.

Does the engineer need F-Gas certification for P6?

For the second half of Mitsubishi’s action on a PUHZ-W, PUHZ-HW, PUZ-WM or PUZ-HWM unit, yes. Checking the refrigerant charge means connecting gauges to a circuit containing R410A or R32, both fluorinated gases, and only a certified engineer may do that. On the PUZ-WZ Ecodan R290 range the refrigerant is not an F-gas, so the certificate is not the legal test; it is a highly flammable hydrocarbon and Mitsubishi restrict the work to trained installers. The first half, the L3 flow checks, any competent heating engineer can do.

Could the plate heat exchanger already be damaged?

If P6 did its job, no; that is what the protection is for. The damage happens when the protection is ignored and the code is reset repeatedly through a cold spell. A single P6, cleared and investigated, is the system working.

Written by

Andrew Pickett

Researcher and writer

Last updated

Technical review

Not reviewed by an engineer

No engineer has read this page. Severity follows what the manufacturer publishes, and we would rather tell you that than let a byline imply a sign-off.

What we check instead

Sources and how we verified this

We establish the facts from the sources below and then write the explanation ourselves. We do not copy manufacturer wording and we do not host their manuals.

  • Manufacturer technical and service documentation
  • Manufacturer support portal

This page has not been reviewed by an engineer, and we would rather tell you that than imply otherwise. The severity rating follows what the manufacturer publishes: where they say isolate the appliance and call someone, so do we.

Read our full verification process

Was this page helpful?